1 Scope
-
— have a rated voltage up to 1 000 V;
-
— are intended for direct-on-line or star-delta starting;
-
— are rated on the basis of duty type S1;
-
— are constructed to any degree of protection and explosion protection.
NOTE 1 It is not expected that all manufacturers will produce machines for all eight designs. The selection of any specific design in accordance with this document will be a matter of agreement between the manufacturer and the purchaser.
NOTE 2 Designs other than the eight specified may be necessary for particular applications.
NOTE 3 It should be noted that values given in manufacturers' catalogues may include tolerances in accordance with IEC 60034‑1.
NOTE 4 The values tabled for locked rotor apparent power are based on r.m.s. symmetrical steady state locked rotor currents; at motor switch on there will be a one-half cycle asymmetrical instantaneous peak current which may range from 1,8 to 2,8 times the steady state locked rotor value. The current peak and decay time are a function of the motor design and switching angle.